1. Load figures

For every selected device we use three inputs: running watts, startup watts and usage (duty cycle).

Total running load assumes all selected devices are on at the same moment:

Running load (W) = Σ running watts × quantity

Average load accounts for devices that cycle on and off. A refrigerator compressor, for example, might run around 40% of the time:

Average load (W) = Σ running watts × quantity × usage
Energy per 24 h (Wh) = Average load × 24

Startup peak assumes everything else is already running and one device is starting. It adds the single largest extra startup draw (startup watts − running watts):

Startup peak (W) = Running load + max(startup watts − running watts)

2. Usable energy and runtime

Not all of a battery’s rated capacity reaches your devices. Stations keep a reserve and the inverter loses energy converting DC battery power to 120 V AC. The calculator applies two adjustable factors:

Usable energy (Wh) = Capacity (Wh) × usable capacity (90%) × inverter efficiency (85%)
Estimated runtime (h) = Usable energy (Wh) ÷ Average load (W)

Worked example: a refrigerator (150 W, 40% usage) and a router (20 W, always on) on a 1,000 Wh station. Average load = 150 × 0.4 + 20 = 80 W. Usable energy = 1,000 × 0.90 × 0.85 = 765 Wh. Runtime ≈ 765 ÷ 80 ≈ 9.6 hours (about 9 h 34 min).

The defaults of 90% and 85% are general assumptions, not values for any specific product. You can change both under Advanced assumptions.

3. Rating checks

4. Example data

Every value below is an Estimate – a rounded, generic number chosen for illustration. None are measurements, and none come from a manufacturer’s specification. Real devices can differ greatly.

Example appliance estimates
DeviceRunning WStartup WUsage
Refrigerator (full-size)1501,20040%
Chest freezer8080040%
Microwave oven1,5001,8003%
Wi-Fi router + modem2020100%
LED TV (about 50")100100100%
Laptop charger6060100%
Phone charger1010100%
Box fan75150100%
Electric space heater1,5001,50050%
LED light bulb1010100%
CPAP machine (no humidifier)404033%

Power station presets

The presets are generic capacity classes, not real products. They exist only as a starting point.

Generic example power station classes
Example classCapacityContinuousSurge
Example compact station (300 Wh)300 Wh300 W600 W
Example mid-size station (1,000 Wh)1,000 Wh1,000 W2,000 W
Example large station (2,000 Wh)2,000 Wh2,000 W4,000 W
Example home-backup station (3,600 Wh)3,600 Wh3,000 W6,000 W

5. Limitations

6. Testing and future data

The formulas live in a separate, dependency-free module covered by automated tests (load sums, duty cycles, surge selection, efficiency factors, rating thresholds, input validation and formatting). The data model already distinguishes estimates from measured values and verified manufacturer specs, so real measurements and specific power station models can be added later – each clearly labeled with its source and date.